Water-Cooled Chiller Sizing Guide: Capacity, Water Conditions & RFQ
Specify the actual evaporator and condenser conditions first. Then compare manufacturer selections, equipment scope and project RFQs on a consistent basis.
Request Chiller TDS & Quote on WhatsApp ↗
Published 9 October 2026 · SongXin HVAC technical procurement guide · Example calculations are illustrative, not model-specific test data.
Who this guide is for: mechanical engineers, EPC teams, industrial buyers and importers preparing a water-cooled chiller technical enquiry. This is a specification method, not a certified selection report for a particular model.
Start with the project duty, not a nominal tonnage
A water-cooled chiller selection begins with the cooling duty the completed system must deliver at a defined condition. The design engineer should state the required net chilled-water duty, design chilled-water temperatures, permitted flow and pressure drop, site condenser-water conditions, operating profile and reliability requirements. A nameplate capacity measured under different conditions does not prove the installed plant can meet the actual duty.
Quick answer: establish a common operating basis, calculate fluid-side duty, then request the manufacturer’s model selection showing available capacity and electrical input at the project’s actual evaporator and condenser conditions. Confirm plant auxiliaries and exclusions before comparing prices.
Step 1 — Define the design cooling load and operating profile
Specify the simultaneously required duty, not the sum of unrelated individual equipment nameplates. For a commercial building, a qualified designer should document load diversity, ventilation, process loads and expected part-load operation. For process cooling, determine peak and sustained duties, allowed process temperature variation and consequences of interruption.
- Design cooling load at the defined project condition, in kW or refrigeration tons.
- Expected minimum, typical and maximum duty over the operating year.
- Hours per day, days per year, and any phased capacity expansion.
- Duty/standby strategy, access for maintenance, and acceptable outage conditions.
Keep capacity margin separate from redundancy. An N+1 requirement concerns maintaining the required duty after one unit becomes unavailable; adding a generic percentage to nameplate capacity does not establish that outcome.
Step 2 — Specify chilled-water temperatures, fluid and flow
For a single-phase fluid circuit, an approximate heat balance is Q = ṁ × cp × ΔT. Here Q is heat-transfer rate in kW, ṁ is mass flow in kg/s, cp is fluid specific heat in kJ/(kg·K), and ΔT is entering minus leaving chilled-fluid temperature in kelvin. For water near ordinary HVAC conditions, a preliminary check may use a specific heat close to 4.18 kJ/(kg·K), but the design must use appropriate properties at its fluid temperature and concentration.
Illustrative calculation only: for a hypothetical 500 kW evaporator duty and 5 K water temperature rise, mass flow ≈ 500/(4.18 × 5) = 23.9 kg/s. If a screening calculation assumes water density of 1,000 kg/m³, that is about 86.1 m³/h. These values are not a SongXin model specification or a final pump selection. The verified fluid properties, actual plate/shell heat-exchanger pressure drop, bypass and minimum-flow limits must come from the selected equipment and system design.
For glycol or other mixtures, do not reuse plain-water density, heat capacity, viscosity or freezing characteristics. Ask for an approved fluid data sheet, concentration, intended corrosion protection and a compatible manufacturer selection.
Step 3 — Establish the condenser-water and heat-rejection basis
Water-cooled chiller performance depends on the heat-rejection circuit. State condenser-water entering and leaving temperatures, design condenser-water flow, available pump head and the design outdoor wet-bulb basis for the cooling tower. Require a coordinated proposal showing how these conditions will be achieved during expected outdoor conditions and at partial load.
The condenser generally rejects both the evaporator heat absorbed from the chilled-water system and the heat associated with compressor and other package electrical input. Accordingly, the tower duty is not identical to the evaporator cooling capacity. Ask the supplier or plant designer to provide a heat-rejection balance at the quoted operating points, instead of simply sizing the tower from evaporator tons.
- Cooling tower is existing, new, or outside the supplier’s scope?
- Condenser-water quality, treatment, fouling assumptions and freeze protection?
- Minimum condenser-water temperature and control limitations for the proposed compressor?
- Condenser pump duties, redundancy and distribution-system pressure drop?
Step 4 — Compare capacity and power on an equivalent basis
When comparing quotations, make both suppliers declare the same project cooling load, chilled-water supply/return conditions, condenser-water conditions, fluid type, electrical supply and measurement boundary. Request available evaporator capacity, compressor/packaged input power, condenser heat rejection and part-load performance at those declared conditions.
Do not equate a quoted COP to complete cooling-plant efficiency unless pumps, tower fans and other auxiliaries are consistently included. For project economics, calculate energy across expected operating points rather than multiplying one rated COP by annual hours. Standards such as AHRI 550/590 provide applicable chiller performance rating methods in relevant markets; a general reference is not proof that an individual SongXin model holds a certification.
Step 5 — Confirm installation, control and reliability
Equipment must fit the plant room and operate as part of a complete system. Verify unit dimensions and service clearances, lifting and replacement routes, installation loads, electrical supply, startup current if relevant, acoustic constraints, controls and BMS interface requirements. For hydraulic design, obtain evaporator and condenser design pressure drops and minimum/maximum allowable flows from the selected model.
Define alarms, pump-proving interlocks, flow switches, standby sequencing and failure response with the responsible controls engineer. If the project requires N+1 capacity, demonstrate that the surviving equipment and its associated power, water and controls can serve the required duty under the specified failure case. Do not assume redundancy merely from the number of installed machines.
A project comparison checklist
| Selection item | Project data / evidence to request | Why it matters |
|---|---|---|
| Required duty | Cooling load (kW), design and part-load profile | Capacity at actual demand |
| Evaporator fluid | Type, concentration, supply/return temperature, flow | Heat-transfer and freezing basis |
| Condenser water | Entering/leaving temperatures, tower wet-bulb basis | Available capacity and power |
| Pressure & pumps | Evaporator/condenser pressure drops and flow limits | Pump and hydraulic design |
| Electrical | Voltage, phase, frequency and electrical schedule | Local grid and site compatibility |
| Performance | Manufacturer’s selection report at stated conditions | Comparable capacity and efficiency |
| Site constraints | Dimensions, access, installation, sound criteria | Constructability and maintenance |
| Scope | Chiller, pumps, tower, controls, spares, commissioning | Comparable commercial offers |
| Documentation | Model TDS, drawings, applicable test/certification evidence | Technical due diligence |
Mistakes that create expensive procurement surprises
- Comparing nominal tons without matching water temperatures and design ambient or tower conditions.
- Pricing the chiller package but omitting condenser-water pumps, tower, water treatment and controls.
- Assuming one generic water temperature or flow applies to every compressor and heat exchanger design.
- Comparing full-load chiller COP without separately considering part-load operation and plant auxiliaries.
- Treating illustrative calculations or another manufacturer’s data as a selected SongXin unit’s performance.
- Leaving service access, shipping splits, startup, spare parts and warranty responsibility undefined.
Ready-to-send water-cooled chiller RFQ brief
Copy these details into an email or send them through the WhatsApp enquiry button below. Unknown values can be identified as “to be confirmed”; a reliable early-stage enquiry does not require pretending the project design is complete.
Cooling duty: [design kW or TR; load profile]
Chilled fluid: [fluid, concentration, supply/return °C, flow if known]
Condenser water: [entering/leaving °C; existing or new tower]
Electrical: [voltage / phase / frequency]
Reliability: [N, N+1 or other defined failure case]
Required documents: [selection report, TDS, drawings, interface schedule]
Commercial scope: [quantity, project timeline, delivery country, desired Incoterm and exclusions]
For an accurate quotation, SongXin should confirm which model and operating conditions can actually be supplied, the source of any performance figures and the scope of included equipment. A response that only repeats “high efficiency” without selected-condition evidence should not be considered a complete engineering proposal.

Request model-specific technical data from SongXin HVAC
Send the project brief above and ask the technical team to confirm actual available models, selected-condition cooling performance, included auxiliaries, documentation and delivery scope. WhatsApp is the direct enquiry channel; no web form is needed.
Send Water-Cooled Chiller RFQ on WhatsApp ↗
Related: Water-Cooled Chiller Product | Technology Comparison.